Responses to Questions on Data Centers From Secaucus Residents

Posted Fri, Oct 16, 2026, From Secaucus Township
Responses to Questions on Data Centers From Secaucus Residents

At the September 22, 2026, Town Council meeting, some residents raised questions relating to data centers in Secaucus. Mayor Gonnelli and council members advised residents that they may not have correct information on questions raised and committed to share answers at the next council meeting. These are the responses that were shared at the Town Council meeting on October 13, 2026.

1. What was the damage to wildlife and plants from the spill?

Town of Secaucus: According to statements issues by the NJDEP they have not identified any damage to wildlife or plants from the spill. We expect the DEP to issue a final report with their findings. At this time, they have not advised us on the timing for the release of their report.

2. Since Equinix has decided to expand its data center construction at 275 Hartz Way can you tell us how much bigger this site will be?

Town of Secaucus: The current building, which was the site of Burlington Coat Factory, was approximately 198,396 sq. feet of gross floor area over 2 floors. The New data center will be a total of 369,968 square feet over 4 floors. The building footprint will be slightly smaller, however, will be taller than the current building. The new facility would support connections that businesses rely on every day, including online banking, hospital services and online video streaming.

3. How big is the Equinix center going to be at 275 Hartz Way?

See answer to question #2.

4. Mayor, you state we will not have “AI” data centers. Why would the data center spend the money on the specialized cooling system if they are not planning on AI workloads? Doesn’t that mean they are anticipating AI workloads? What’s to stop them from converting later?

CoreSite: While some of CoreSite’s customers do run AI applications such as inferencing, research, banking, networking, etc, our data centers are not AI data centers. We are not large hyperscale AI factories, but rather colocation data centers housing dozens of customers under one roof to leverage shared services. Modern compute technology continues to increase in efficiency and therefore density. As processing moves from CPU, to GPU, to Quantum computing, equipment densities continue to increase. To keep up with high-performance computing the cold air or liquid needs to move closer to the chips, this is accomplished via rack level and direct to chip cooling. The use cases for this range from online banking transactions to financial market trading, to video and content streaming, to online gaming. The “specialized” cooling to which you refer is simply bringing the cooling medium closer to the workloads within the computer room. Gone are the days of inefficiently “flooding” rooms with cold air. Modern cooling technology, bringing cooling directly to where it is needed, is much more efficient. Long before large AI models were being developed in hyperscale facilities, a research university was doing high-density compute which leverages liquid cooling for biomedical research and development at our facility, this is ongoing today. We are not a Hyperscale AI provider, but rather a retail colocation provider who needs to remain flexible to meet customer needs.

Equinix: There are no cooling systems specialized for AI installed in our Secaucus IBXs. Our current facilities in Secaucus use common chilled-water cooling systems. The only specialization Equinix has applied to these systems is to maximize energy efficiency. The chilled water serves air handling systems in our IBX data halls, which cool computing load through an air circulation process.

The chilled water planned for our future NY10 site could also be used by customers interested in using direct to chip liquid cooling. The use of liquid cooling capability does not mean NY10 is being developed as a dedicated AI data center. The prevalence of direct-to-chip liquid cooling for computing equipment is an emerging computing industry trend to further drive operational energy efficiency. It is increasingly being adopted across the computing industry because it can improve energy efficiency for certain types of equipment, not solely for AI chips.

More importantly, NY10 is not designed to operate as the type of large-scale AI training facility that has raised concerns in some communities. Dedicated AI training campuses are typically much larger facilities with substantially higher power requirements, often measured in hundreds or even thousands of megawatts. NY10 could not reach the size of the large-scale AI training facilities.

Could computing equipment evolve over time? Yes. Customer technology changes continuously, and we cannot predict every future workload that customers may deploy. However, any future use of the facility would remain subject to the site's physical design, power availability, utility constraints, and applicable regulatory requirements. Installing standard cooling infrastructure today does not create the capability to transform NY10 into a large-scale AI training campus.

For context, Equinix uses a common chilled-water cooling system. The system supports cooling of the data halls and can also support customers that use liquid-cooled servers. Direct-to-chip liquid cooling is becoming more common across the computing industry because it can improve operational efficiency, but its presence alone does not mean that a facility is dedicated to AI training.

5. Have we signed a non-disclosure agreement with any of these data centers? If someone came to you with a non-disclosure, would you sign it?

Town of Secaucus: Neither the Mayor nor any Councilmembers have executed any nondisclosure agreements with data centers, nor have they ever been approached to do so.

6. The evaporators at the top of data centers breed bacteria and if not treated correctly can spawn disease like legionnaires disease. The evaporators send a mist into the atmosphere and that is sent aloft into the surrounding area. Legionnaires disease has been documented numerous times with numerous deaths attributed to these towers. In 2026 alone Legionella was detected in 56 different cooling towers on the upper east side of NYC alone. What steps are you taking to make sure this doesn’t happen here in town?

Core Site: Cooling towers are a standard part of commercial, industrial, and residential cooling systems. Our cooling towers are cleaned and maintained beyond the regulatory requirements. NJ 2188 is the state law governing water and cooling tower management plans for buildings. Under NJ 2188 water management programs must align with NJ Department of Health recommendations and ASHRAE (American Society of Heating, Refrigeration, and Air-Conditioning Engineers) Standard 188.

Legionella breeds in untreated water between 77degF – 113degF. We operate our condenser water systems with treated water typically between 70degF – 85degF.

At CoreSite we have many levels of protection beyond the standards in place to ensure our cooling towers remain clean and safe. The following is our standard:
  1. Every cooling tower is equipped with an automatic chemical control system to regulate cleanliness, mitigate biological growth in the system, inhibit corrosion, and increase efficiency.
  2. A 3rd party vendor is on site at minimum monthly to check all chemical feeders and water chemistry.
  3. A separate 3rd party water chemistry vendor conducts monthly water analysis as well as an audit of the first vendor’s work.
  4. Quarterly physical cleaning of all cooling towers.

Note: There are dozens of cooling towers in town, including 12 at Harmon Cover Towers, 4 at the hospital, 2 at the Hudson County Schools of Technology, multiple on the office buildings in town and at Harmon Meadow (Children’s place, NBA offices, the Vitamin Shoppe, etc.)

Equinix: Equinix daily treats water in cooling systems at each of our facilities to keep it safe. The program includes:
  • Adding chemicals called biocides to the water that kill bacteria, including those that cause Legionnaire’s disease (Legionella). These chemicals are regularly checked and adjusted to stay effective.
  • Third-party testing of the water for Legionella every three months.
  • Having outside water-treatment specialists run the program, meeting or exceeding all required regulations.

The cooling towers are also designed to prevent problems:
  • They’re separated so that mist from one tower can’t be pulled back into another (called “re-entrainment”)
  • The water inside keeps circulating continuously to avoid situations like those that can occur in the cooling towers on the upper east side of New York City, where water can sit and let bacteria grow.

Together, this combination of tower design, continuous water circulation, and ongoing treatment is intended to eliminate the presence of Legionella.

7. The water that cools these data centers leaves behind mineral deposits as the water evaporates, these minerals are corrosive in nature. Is there a schedule that will be kept by town inspectors to make sure the data center systems are not in jeopardy of failure? Further, when the data centers clean these mineral deposits, what chemicals and corrosives are used in cleaning? What steps are and will be taken to make sure these caustic chemicals do not get into our water supply and water ways?

CoreSite: Much like the previous question our cooling towers and the water in them are maintained regularly. As water is evaporated and recycled within the system conductivity in the water gradually increases due to dissolved solids present in the water, namely sodium chloride (salt), calcium, magnesium, and silica (sand). When conductivity reaches a predetermined level (typically 3 – 4 cycles of concentration) the cooling tower controls call for a valve to open to discharge water into the town’s sanitary system and fresh water is brought into the cooling towers. The water discharged to the sanitary system goes to the water treatment center where it is further processed.

Equinix: The minerals in our cooling water mostly come from the city’s municipal water supply. Here are the steps we take to address minerals in the water:
  • We test the incoming city water at the outset of the project. The results tell us how many times the water can be reused in the cooling system.
  • Through our cooling water reuse process, the system evaporates water and the concentration of minerals increases.
  • An active sampling system monitors the water in the system and determines when concentrations of these minerals are such that they could adversely impact pipework and equipment.
  • When the water can no longer be used, we discharge a portion of it into the municipal sanitary sewage system. From there, it goes to the municipal water treatment facilities.

To further protect equipment and pipework, we use a small set of water-treatment products. They are used to inhibit corrosion, protecting metal pipes and equipment from rusting. We also use biocides and disinfectants to kill bacteria and other organisms in the water. Water softening treatments keep the minerals in “hard” water (i.e., water containing comparatively high levels of minerals) from leaving scale deposits.

8. Does every data center use biodegradable cleaning products? Is it toxic? What are we doing to regulate these cleaning products? Can we have our environmentalist check?

CoreSite: We use industry standard chemicals to treat our cooling tower water. Some are biodegradable and some such as chlorine are not biodegradable. As previously mentioned, all cooling towers are cleaned and maintained according to regulatory requirements. NJ 2188 is the state law outlining water and cooling tower management plans for buildings.

The Secaucus MUA is in the process of conducting an analysis of data center cooling systems, water usage, and water chemistry.

We have all SDS information on site available to the AHJ and Fire Department.

Equinix: Our data centers use standard janitorial products, the same kinds used in typical office buildings. These are commercially available products used for routine cleaning, such as floors, restrooms, and surfaces.

9. What is the total number of “antennae farms” and the number of microwave antennas contained within these farms. Are they point to point? Are they cellular/MARCO Based? (the resident was inferring there are many antennas on the roofs of data centers)

CoreSite: CoreSite does not have “antennae farms” or a large antennae structure or mast. There are approximately 50 antennae combined between CoreSite NY2 and NY3. The antennae on the buildings are property of our colocation customers. The antenna types are mainly GPS, cellular, and radio. There are no large microwave or broadcast dish antennae on CoreSite NY2 or NY3. Antennae are registered by customers with the FCC if required.

Note: There are antennae on many non-data center buildings in town including: Impreveduto Towers, Harmon Cover Towers, Town Hall, schools, fire houses, and commercial buildings throughout town. There are also large broadcast antennae and dishes on Radio Ave and at MLB Network.

Equinix: Many of our customers need antennas at our facilities to support their own communications. Some of our facilities in this area support the world’s largest financial interconnection networks. This is where banks, trading firms, telecommunications carriers, media companies and other networks connect to each other.

To make those connections, some customers install communications equipment on the facility rooftops. This equipment can include:
  • Point-to-point microwave line-of-sight (LOS) communications equipment, which connect two locations directly.
  • GPS timing receivers, which pick up satellite signals to precisely synchronize systems.
  • Other communications equipment that link customers to outside networks.

The operation of this equipment follows requirements outlined by the FCC. Specifically, LOS systems are power-limited antenna which produce a highly focused signal aimed at a receiving target. This operation is not hazardous to the public because the signal source is non-ionizing radiation and its directional beams are positioned far out of reach.

10. Have there ever been any catastrophic events at the data centers in Secaucus?

No. One data center had a minor fire years ago that, we believe, impacted their operations for a couple of days.

CoreSite: None at CoreSite.

Equinix: No. In more than two decades of operating in Secaucus, we have not had a catastrophic event at our facilities, such as a major fire, explosion, or structural failure. Our sites are built with multiple layers of safety systems, and we monitor and test them regularly.

We also want to be upfront about the NY2 fuel leak. While we are taking the recent diesel spill incident very seriously, it was not of the size or impact that would generally be considered a catastrophic event. It was still a serious incident, and we take it very seriously, and we’ve shared what we currently know in our report. We’re continuing remediation, addressed the tank which experienced valve failures, and will keep sharing updates as the work progresses.

11. Are we going to have that data center at 215 County Ave well-lit like a warehouse at nighttime? What about sound levels? (concerned about people sleeping).

CoreSite: CoreSite NY4 will have surface lighting in the parking lot for safety. All lighting on property will be in accordance with zoning regulations & building codes.

CoreSite NY4 at 215 County Ave will adhere to all building codes and zoning requirements regarding sound just as we do at our NY2 and NY3 facilities. During the variance meeting for 215 County Ave, CoreSite offered to conduct additional sound testing upon completion of the facility. This testing is above and beyond the typical requirements for construction. The board agreed and this was memorialized in the variance approval.

CoreSite has requested no variance for lighting or sound at any property in Secaucus including 215 County Ave.

12. In Vineland NJ, the data center was fined 1 million for pollution for illegally operating natural gas generators that release harmful pollution. Have you thought about that happening here? Are you concerned?

This statement was incorrect. The data center in Vineland was fined by the state because they were operating natural gas generators without the proper permits. They were not fined for the release of harmful pollutants into the air.

13. How are we holding Equinix accountable to make sure they are ensuring a thorough remediation?

Town of Secaucus: The NJDEP is the agency that is overseeing the cleanup of the diesel spill and they have jurisdiction. As stated earlier the NJDEP will issue a final report and has been keeping us informed as to the status of the cleanup. The Mayor also asked that Equinix keep us informed on all developments which they have been doing. As the Mayor indicated at the outset, Equinix released the results of their findings last night and we posted the link to those documents this morning.

14. Why are we allowing so many data centers in Secaucus?

Town of Secaucus: The first data center came to Secaucus 25 years ago and others have been constructed over the years. Data Centers were and remain a permitted use in the NJSEA district. The town did not actively go out and market for data centers to make Secaucus their home. It naturally happened largely in part to our proximity to New York City and the strong fiber network installed by public utilities.

15. Has anyone visited the cleanup effort at the creek from the spill? How can we trust you to clean it properly?

Town of Secaucus: Numerous officials and town employees visit the cleanup site. Officials from the NJDEP, EPA, Coast Guard and other government agencies have also been onsite. As previously advised, the NJDEP is ensuring the cleanup is completed and meets all their standards.

16. Are they planning to replace diesel powered generators with lithium-ion batteries at the data centers?

CoreSite: No, emergency diesel generators will remain in place. Batteries are part of the UPS system in the building. Various battery technology is utilized such as VRLA and Lithium-Ion. CoreSite is always researching and investing in new technology to increase efficiency, better serve our customers, and our communities.

Equinix: Equinix does not use large scale Battery Energy Storage Systems (BESS) at our New Jersey facilities. Equinix does not have plans for installation of such systems at our premises to replace diesel generation.

Equinix IBX needs emergency backup power systems to ensure the facilities and customers they support can remain online through extended utility outages (including the US financial services system, health and medical records, and other critical services). Standby diesel-driven power generation is used at our Secaucus IBX to provide a reliable source of power throughout any outage events. For example, during Superstorm Sandy Equinix stayed online for 5 days without utility power. This continuous operation kept the critical services hosted in our facilities online during the storm, mitigating even more harm to the region and country.

17. Do the data centers meet national safety regulations?

CoreSite: All CoreSite data centers meet all local building codes and standards, which are at a minimum the national standard. Some examples of these standards include the NFPA 70 (National Fire Protection Associate) which includes the National Electric Code, NFPA 70E, ANSI/ASHRAE 90.4 (Energy Standard for Data Centers), OSHA, NJ 2188.

Equinix: Yes. Our facilities either meet or exceed regulatory requirements and applicable building codes. Relevant aspects of our facilities in Secaucus are reviewed by the New Jersey Department of Environmental Protection (NJDEP), utility providers such as PSE&G, building and fire officials, local agencies, the Meadowlands regulatory framework, and other agencies.

Before any of our projects in the area move forward, we must secure approvals covering the environment, utilities, safety, land use and construction. However, oversight doesn’t end once the building is open. Throughout the life of the facility, inspections, monitoring and permit requirements continue to apply.

18. Are the data centers insured?

CoreSite: Yes

Equinix: Yes, the company maintains standard insurance policies including property and general liability.

19. How is there not going to be another spill again?

Town of Secaucus: We cannot guarantee that no commercial property will ever experience a spill again. The commercial properties are required to meet all Federal, State and local building requirements during construction and must also meet required standards for inspection of their systems.

20. Is the DEP currently a privatized agency, and if so, what date did the privatization begin?

Town of Secaucus: The DEP is not a privatized organization and is an entity of the State of New Jersey. The DEP is overseen by Ed Potosnak, who was appointed by the Governor.

21. Why has the Town’s Environmental Coordinator not been in attendance at council meetings to provide her insight?

Town of Secaucus: The Town’s environmental coordinator does not handle any matter related to spills or environmental cleanups and has no expertise in these areas. The Town’s environmental department oversees issues such as recycling compliance, reporting on recycling tonnage, overseeing our community gardens, overseeing our composting programs, assisting with our tree inventory, etc. The department does not, in any way, oversee the environmental responsibility of commercial entities. This is generally done by the NJDEP or other State agencies.

22. Latest update from the DEP dated 10/7/26:

The contractor for Equinix continues to remediate any residual oil and debris in the drainage channel. In addition, Equinix has retained a Licensed Site Remediation Professional to investigate the nature and extent of any impacts and to oversee the cleanup. This investigation is ongoing and will determine next steps. DEP Office of Emergency Management, who was on scene early on did not observe impacts to the Anderson Creek or its associated wetlands, the Hackensack River, drinking water, or wildlife. The emergency response phase of this incident is complete and the LSRP will now assume oversight of both the clean-up and investigation to thoroughly characterize any impacts. DEP programs responsible for enforcement of relevant environmental laws are also investigating the incident.